English -- Ventilation of Health Care Facilities

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2017-10-18T11:07:01Z
date available2017-10-18T11:07:01Z
date copyright2016.11.30
date issued2016
identifier otherTVLVSFAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;jsessionid=435F2D89F77216F55ECC40BAF539160F/handle/yse/235188
description abstractScope: General Requirements a. Locate humidifiers within air-handling units or ductwork to avoid moisture accumulation in downstream components, including filters and insulation. b. A humidity sensor shall be provided, located at a suitable distance downstream from the steam injection source. c. Controls shall be provided to limit duct humidity to a maximum value of 90% rh when the humidifier is operating. d. Duct takeoffs shall not be located within the humidifier’s absorption distance. e. Humidifier steam control valves shall be designed so that they remain off whenever the air-handling unit is not in operation.
languageEnglish
titleASHRAE 170 ADD Mnum
titleEnglish -- Ventilation of Health Care Facilitiesen
typestandard
page6
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2016