Ventilation of Health Care Facilities
ASHRAE 170 INT 4
| contributor author | ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. | |
| date accessioned | 2020-07-27T20:51:04Z | |
| date available | 2020-07-27T20:51:04Z | |
| date issued | 2019 | |
| identifier other | NRYBJGAAAAAAAAAA.pdf | |
| identifier uri | http://yse.yabesh.ir/std;query=auth/handle/yse/280384 | |
| description abstract | A return air, variable air volume air handling system contains an air handling unit (AHU) equipped with an airside economizer. (2 ACH)(200)(9)/60 = 60 cfm of outdoor air minimum is required in each patient room. The AHU is designed to be controlled to always bring in a minimum of (60 cfm OA)(50 patient rooms) = 3,000 cfm of outdoor air. Paragraph 7.1.a.6 allows the use of method 7.1.a.6.i whereby: “i. System minimum outdoor air quantity for an air-handling system shall be calculated as the sum of the individual space requirements as defined by the standard.” Topics outdoor air;outdoor air cfm;background ahu;outdoor air cfm minimum;outdoor air minimum cfm | |
| language | English | |
| title | Ventilation of Health Care Facilities | en |
| title | ASHRAE 170 INT 4 | num |
| type | standard | |
| page | 4 | |
| status | Active | |
| tree | ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2019 | |