Ventilation of Health Care Facilities
ASHRAE 170 INT 16
| contributor author | ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. | |
| date accessioned | 2020-07-27T20:51:06Z | |
| date available | 2020-07-27T20:51:06Z | |
| date issued | 2019 | |
| identifier other | VQYBJGAAAAAAAAAA.pdf | |
| identifier uri | http://yse.yabesh.ir/std;query=auth/handle/yse/280389 | |
| description abstract | ASHRAE/ASHE Standard 170 Section 6.4 states the required filtration for spaces within this facility. In particular, Nursing facilities have the following filtration requirements Filter bank #1 MERV 13 filter bank #2 NR (not required). Section 6.4 states "All of the air provided to a space shall be filtered in accordance with Table 6.4, except as otherwise indicated in Section 7.1 for spaces that allow recirculating HVAC room units. | |
| language | English | |
| title | Ventilation of Health Care Facilities | en |
| title | ASHRAE 170 INT 16 | num |
| type | standard | |
| page | 1 | |
| status | Active | |
| tree | ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2019 | |
| contenttype | fulltext |