ASHRAE 170 INT 8

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2020-08-03T11:59:59Z
date available2020-08-03T11:59:59Z
date issued2020
identifier otherTNTPMGAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;query=autho162/handle/yse/280684
description abstractHowever, §7.1.a.6.i is not permitted by ASHRAE Standard 62.1. I don't believe Standard 170 means to allow systems with Standard 62.1 space to use a method of calculation that fails to comply with Standard 62.1. Any system serving spaces whose ventilation rates come from ASHRAE Standard 62.1 must use §7.1.a.6.ii and shall not use §7.1.a.6.i. Applicability and compliance with Standard 62.1 is as defined by the authority having jurisdiction and the user and not addressed in Standard 170. Any system serving spaces whose ventilation rates come from ASHRAE Standard 62.1 should comply with Standard 62.1.
languageEnglish
titleVentilation of Health Care Facilitiesen
titleASHRAE 170 INT 8num
typestandard
page2
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2020