ASHRAE 170 INT 9

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2020-08-03T11:59:59Z
date available2020-08-03T11:59:59Z
date issued2020
identifier otherWNTPMGAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;jsery=autho162sear/handle/yse/280686
description abstractThis request for interpretation refers to the requirements in ANSI/ASHRAE/ASHE Standard 170-2017, Section 7.4.1a and Note o to Table 7.1, regarding operating room maximum velocity of diffuser. Section 7.4.1a specifies an average diffuser velocity (for a primary supply diffuser array) between 25 to 35 cfm/ft2. Is 35 cfm/ft2 the maximum allowed average? Table 7.1 Note o allows the designer to exceed the minimum indicated ranges and distribution methods. 35 cfm/ft2 is not the maximum velocity for a primary supply diffuser array, and the designer is allowed to increase that velocity above the minimum requirement
languageEnglish
titleVentilation of Health Care Facilitiesen
titleASHRAE 170 INT 9num
typestandard
page1
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2020
contenttypefulltext