Show simple item record

Optimization of the Cooling Tower Condenser Water Leaving Temperature Using a Component-Based Model

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2017-09-04T18:38:30Z
date available2017-09-04T18:38:30Z
date copyright01/01/2011
date issued2011
identifier otherJPXTKEAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;query=autho162sear79D/handle/yse/220280
description abstractABSTRACT
This study investigates the optimization of the cooling tower condenser-water leaving temperature using a component- based model. This model consists of a chiller, a condenser-water pump, and two cooling towers. The chiller is modeled with a Gordon-Ng model for vapor-compression chillers with variable-condenser flow. The cooling tower is simulated with an effectiveness-NTU model. The pump power is calculated from the pump flow rate, pump head, and efficiency. This optimization problem is formulated as that of minimizing the total power of the chiller, pump, and fans by selecting an optimal cooling tower condenser-water leaving temperature at given weather conditions, chiller load, chilledwater leaving temperature, and condense-water flow rate. The model is applied in an example chiller CW system, and a generalized reduced gradient solver is used to search the optimal cooling tower approach setpoint. Simulation results show that the optimal cooling tower approach reset schedule can be approximated with two straight lines. Significant energy savings could be achieved if compared with the scenario with a constant cooling tower condenser-water leaving temperature. Further simulations show that the chilled-water leaving temperature, chiller part-load ratio, and the climate zones the plant locates in have a minor effect on the optimal approach reset schedule. A higher condenser-water flow rate per cooling ton leads to a higher optimal cooling tower approach, but this effect can be neglected for a system with a constant CW flow rate. The approach setpoint reset schedule that yields optimal control depends on the performance characteristics of the chiller and the cooling tower.
languageEnglish
titleASHRAE LV-11-027num
titleOptimization of the Cooling Tower Condenser Water Leaving Temperature Using a Component-Based Modelen
typestandard
page11
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2011
contenttypefulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record