description abstractSalvatore Cataldi, BELIMO Automaton AG, Brunnenbachstrasse 8, Hinwil, Switzerland, CH-8004. This request for interpretation refers to the requirements presented in ANSI/ASHRAE Standard 135-2016, Clause K.1.12, regarding devices claiming conformance to DS-COV-B. In Clause 13.1 the standard says: It is responsibility of the COV-Server to maintain the list of active subscriptions for each object that support COV Notification. This list of subscriptions shall be capable of holding at least a single subscription for each object that supports COV notification. There is a single list of active subscriptions within the device; this list shall hold at least 5 elements, whatever the number of object supporting COV notification is. Every object supporting COV notification shall be capable of holding at least a single subscription for each object that supports COV notification, till a minimum of 5 concurrent subscription overall. Any subscriber trying to subscribe as the 6th or higher concurrent subscriber might receive an error of type: NO_SPACE_TO_ADD_LIST_ELEMENT.
languageEnglish
titleBACnet - A Data Communication Protocol for Building Automation and Control Networksen
titleASHRAE 135 INT 16num
typestandard
page1
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2019
contenttypefulltext


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record