description abstractASHRAE/ASHE Standard 170 Section 6.4 states the required filtration for spaces within this facility. In particular, Nursing facilities have the following filtration requirements Filter bank #1 MERV 13 filter bank #2 NR (not required). Section 6.4 states "All of the air provided to a space shall be filtered in accordance with Table 6.4, except as otherwise indicated in Section 7.1 for spaces that allow recirculating HVAC room units.