ASHRAE GUIDELINE 36 ADD I

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2020-08-03T12:00:01Z
date available2020-08-03T12:00:01Z
date issued2020
identifier otherBMPDMGAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;query=authoCA5893FD69B749A96159DD6E273C9FCD0Facilities%20Engineering%20Command%226EFDEC9/handle/yse/280694
description abstractThis addendum revises the way the variable-speed series fan is controlled. Currently, the speed tracks the primary airflow. This revision maps the fan airflow set point from a minimum equal to the larger of the ventilation minimum and the primary airflow minimum up to the cooling maximum. The intent is to help ensure that the fan airflow exceeds the primary airflow so that no primary air exits the induction port into the return air plenum, recognizing that the actual fan airflow and actual primary airflow can vary from set point. Note that this will only be effective if the ventilation minimum is larger than the primary airflow minimum, as it will be if the designer is taking advantage of the indirect ventilation capability of the recirculated return air from other zones. If the ventilation minimum is the same as the primary airflow, the sequence is effectively the same as the current sequence. Note: In this addendum, changes to the current standard are indicated in the text by underlining (for additions) and (for deletions) unless the instructions specifically mention some other means of indicating the changes
languageEnglish
titleHigh Performance Sequences of Operation for HVAC Systemsen
titleASHRAE GUIDELINE 36 ADD Inum
typestandard
page12
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2020
contenttypefulltext