Show simple item record

Lessons Learned - Safety Engineering Analysis of Low Hazard Systems Interfaces with High Hazard Systems

contributor authorNASA - National Aeronautics and Space Administration (NASA)
date accessioned2017-09-04T16:47:23Z
date available2017-09-04T16:47:23Z
date copyright09/17/1995
date issued1995
identifier otherWFBEQCAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/110728
description abstractDescription of Driving Event:
During repressurization of a test chamber, ammonia in a test article heat exchanger froze resulting in rupture of the exchanger. The rupture caused pressure to build up in a second test support unit. This second unit had a pressure relief valve, which was released when the pressure exceeded the upper limit, spilling ammonia into the work environment. The facility had to be evacuated.
The root cause of this mishap was failure to treat "low hazard" systems, when connected to ammonia systems, as ammonia hazard systems. Had this been done, the design of the relief valve would have been configured to preclude direct venting of the valve into the facility work environment.
languageEnglish
titleNASA-LLIS-0457num
titleLessons Learned - Safety Engineering Analysis of Low Hazard Systems Interfaces with High Hazard Systemsen
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1995
contenttypefulltext
subject keywordsEmergency Preparedness
subject keywordsFacilities
subject keywordsHazardous/Toxic Waste/Materials
subject keywordsRisk Management/Assessment
subject keywordsSafety & Mission Assurance
subject keywordsTest Facility