Show simple item record

Lessons Learned - JP-4 Fuel Leak

contributor authorNASA - National Aeronautics and Space Administration (NASA)
date accessioned2017-09-04T17:00:36Z
date available2017-09-04T17:00:36Z
date copyright01/20/1994
date issued1994
identifier otherXOZCQCAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/124078
description abstractDescription of Driving Event:
Operations personnel, in an engine test facility, reported that JP-4 fuel was found leaking in the basement of the building. Emergency staff responding to the call discovered that the fuel had originated from the engine on the main floor and had leaked onto a power panel in the basement. The spill was located on and around a 480VAC motor control center that contained breakers and contactors to power the pumps, blowers, and fans in the building.
The building was evacuated due to a potential explosion hazard. The power was turned off and power to the control center terminated. Absorbent pads were placed around the fuel spill for containment and the area barricaded to prevent access.
It was determined that the fuel spill originated from an open fuel return low point drain valve, recently added to the facility, that was not put on the facility drawings. Operations personnel performing a walk-through inspection of the facility did not observe the added drain and therefore were not aware of the presence and open valve position of the drain.
languageEnglish
titleNASA-LLIS-0257num
titleLessons Learned - JP-4 Fuel Leaken
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1994
contenttypefulltext
subject keywordsConfiguration Management
subject keywordsEnergetic Materials - Explosive/Propellant/Pyrotechnic
subject keywordsFacilities
subject keywordsHazardous/Toxic Waste/Materials


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record