EXTINGUISHING SYSTEM, FIRE, FIXED, WET CHEMICAL

contributor authorNAVY - SH - Naval Sea Systems Command (Ship Systems)
date accessioned2017-09-04T17:06:52Z
date available2017-09-04T17:06:52Z
date copyright03/30/2006
date issued2006
identifier otherYGENJBAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/130393
description abstractThis specification covers requirements for pre-engineered wet chemical fixed fire extinguishing systems for protection of deep fat fryers, and doughnut fryers onboard U.S. Navy ships and submarines. The systems covered under this specification are intended for use in new applications, and for backfit into existing wet chemical extinguishing system installations. The current wet chemical extinguishing system utilizes aqueous potassium carbonate (APC) extinguishing agent, in a concentration of 42.4 percent K2CO3 and 52.8 percent water.Intended Use: Pre-engineered wet chemical systems are intended for protection of deep fat fryers and doughnut fryers. A pre-engineered system has predetermined flow rates, nozzle pressures, and quantities of extinguishing agent. These systems have the specific pipe size, maximum and minimum pipe lengths, pie volumes, number of fittings, and number and types of nozzles approved by a testing laboratory.
languageEnglish
titleMIL-DTL-24416Cnum
titleEXTINGUISHING SYSTEM, FIRE, FIXED, WET CHEMICALen
typestandard
page8
statusActive
treeNAVY - SH - Naval Sea Systems Command (Ship Systems):;2006
contenttypefulltext
subject keywordsAqueous potassium carbonate
subject keywordsDeep fat fryer
subject keywordsDoughnut fryer
subject keywordsFire protection
subject keywordsGalley equipment
subject keywordsPre-engineered
subject keywordsSaponification
subject keywordsWet chemical