description abstractDescription of Driving Event:
A hypergol technician erred in the removal of a temperature transducer from a 3-inch hypergol line at the "Pad A" fuel farm, resulting in a major fuel spill and hypergol burns to himself. The installation design of the dry well and temperature transducer provides a means to remove the transducer from the system for replacement or calibration without having to "open" the fluid volume. The dry well installation design is inadequate to preclude an untrained technician or a careless technician from inadvertently removing the dry well from the hypergol propellant line by mistake.
languageEnglish
titleNASA-LLIS-0051num
titleLessons Learned - Dry Well Transducer Installations are Susceptible to Inadvertent Removal; Disposal of Contaminated Wasteen
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1991
contenttypefulltext
subject keywordsEnergetic Materials - Explosive/Propellant/Pyrotechnic
subject keywordsGround Equipment
subject keywordsGround Operations
subject keywordsHazardous/Toxic Waste/Materials
subject keywordsHuman Factors
subject keywordsIndustrial Operations
subject keywordsPackaging Handling Storage
subject keywordsSafety & Mission Assurance