Improving Laboratory Building Energy Performance and Indoor Air Quality Using a Laboratory Air-Handling Unit System (LAHU)

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2017-09-04T17:43:50Z
date available2017-09-04T17:43:50Z
date copyright01/01/2005
date issued2005
identifier otherEEQYHBAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/166947
description abstractThe laboratory air-handling unit (LAHU) system is designed to improve building energy performance and indoor air quality (IAQ) in laboratory buildings. The LAHU system sends more (up to 100%) outside air to the office section and recirculates the office section air to the laboratory section. This theoretical study shows that the potential annual thermal energy savings varies from 20% up to 40% depending on the climate and ratio of office airflow to the laboratory section airflow. The LAHU provides more outside air intake directly to the office section during both cold winter and hot summer months when the IAQ is critical for building occupants. When the office airflow ratio is less than 50%, the LAHU provides close to 100% outside air to the office section at all times.
languageEnglish
titleASHRAE 4752num
titleImproving Laboratory Building Energy Performance and Indoor Air Quality Using a Laboratory Air-Handling Unit System (LAHU)en
typestandard
page10
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2005
contenttypefulltext