Energy Performances of Prototype VAV and CAV Systems under Simulated Humid Tropical Climates

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2017-09-04T18:05:03Z
date available2017-09-04T18:05:03Z
date copyright01/01/2005
date issued2005
identifier otherGIQYHBAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/188005
description abstractThis paper reports the relative energy consumption of prototype VAV and CAV air-conditioning systems under various load conditions simulating those of a typical office building in humid tropical climates such as Singapore 's. Tests were conducted inside two adjoining environmental chambers where space loading was varied from 0.21 7 to 0.295 kW/m2 (68.81 to 93.54 Btu/h ft2 ) with corresponding sensible heat ratio (SHR) ranging from O. 65 to 0.9. The VAV system consistently consumed less energy compared to the CAV system under constant as well as variable load conditions. The percentage energy saving ranged from 21.97%at0.21 7kW/m2 (68.81 Btu/h ft2) to 12.42% at 0.295 kW/m2 (93.54 Btu/hft2) under constant loading, and it decreased with increased space loading. The experiments measured moderate energy savings under the experimental conditions that are assumed to be the typical load condition in Singapore. Because the implementation costs are significant, it appears that a VAV system has marginal economic benefit in Singapore.
languageEnglish
titleASHRAE 4770num
titleEnergy Performances of Prototype VAV and CAV Systems under Simulated Humid Tropical Climatesen
typestandard
page8
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2005
contenttypefulltext