UL Standard for Safety Liquid-Tight Flexible Metal Conduit - Seventh Edition; Reprint with revisions through and including May 3, 2013

contributor authorUL - UL
date accessioned2017-09-04T18:29:37Z
date available2017-09-04T18:29:37Z
date copyright01/17/2013
date issued2013
identifier otherIUBGCFAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/211875
description abstractThese requirements cover the 3/8 (12), 1/2 (16), 3/4 (21), 1 (27), 1-1/4 (35), 1-1/2 (41), 2 (53), 2-1/2 (63), 3 (78), 3–1/2 (91), and 4 (103) trade sizes (metric designators) of liquid-tight flexible steel, aluminum, brass, bronze, copper, and stainless steel conduit. The conduit covered is intended for installation in accordance with the National Electrical Code (NFPA 70) as raceway for wires and cables.
This conduit is for applications in which flexibility of the conduit is necessary during installation, operation, or maintenance and the contained conductors need protection from vapors, liquids or solids.
This conduit is circular in cross section, having an outer liquid-tight, nonmetallic, sunlight-resistant jacket over an inner flexible metal core, and is for use in wet, dry, or oily locations in which the conduit is exposed but is not subject to physical damage. Conduit that is not marked with a temperature designation or is marked ²60 C² is for use at temperatures not in excess of 60°C (140°F). Conduit that is for use in dry or oily locations at a temperature higher than 60°C (140°F) is marked ²____C dry, 60 C wet, 70 C oil res² or ²____C dry, 60 C wet, 70 C oil resistant² with ²80 C² or ²105 C² inserted as the dry-locations temperature.
Conduit that is marked ²80 C dry, 60 C wet, 60 C oil res² or ²80 C dry, 60 C wet, 60 C oil resistant² is for use at 80°C (176°F) and lower temperatures in air, and 60 °C (140°F) and lower temperatures where exposed to water, oil or coolants – that is, to cutting oils and the like in machine-tool and other industrial applications. 1.5 Conduit marked in accordance with 24.4(g) is limited to use in oil free environments. 
Fittings for conduit are covered in the Standard for Conduit, Tubing, and Cable Fittings, UL 514B. 
These requirements do not cover liquid-tight flexible nonmetallic conduit. Flexible nonmetallic conduit is covered in the Standard for Liquid-Tight Flexible Nonmetallic Conduit, UL 1660, and the fittings for this conduit are covered in the Standard for Conduit, Tubing, and Cable Fittings, UL 514B. 
These requirements do not cover flexible metallic tubing. 
These requirements do not cover electrical nonmetallic tubing (ENT).
languageEnglish
titleUL 360num
titleUL Standard for Safety Liquid-Tight Flexible Metal Conduit - Seventh Edition; Reprint with revisions through and including May 3, 2013en
typestandard
page38
statusActive
treeUL - UL:;2013
contenttypefulltext