IEEE C37.101
Guide for Generator Ground Protection
| contributor author | IEEE - The Institute of Electrical and Electronics Engineers, Inc. | |
| date accessioned | 2017-09-04T18:32:59Z | |
| date available | 2017-09-04T18:32:59Z | |
| date copyright | 09/15/2006 | |
| date issued | 2006 | |
| identifier other | JCWGBCAAAAAAAAAA.pdf | |
| identifier uri | https://yse.yabesh.ir/std/handle/yse/215193 | |
| description abstract | This guide has been prepared to aid in the application of relays and relaying schemes for protection against stator ground faults on high-impedance grounded generators. The guide is not intended for the selection of generator or ground connection schemes. Differential relaying will not detect stator ground faults on high-impedance grounded generators. The high impedance normally limits the fault current to levels considerably below the best practical sensitivity of the differential relaying. Separate ground fault protection is then provided. | |
| language | English | |
| title | IEEE C37.101 | num |
| title | Guide for Generator Ground Protection | en |
| type | standard | |
| page | 59 | |
| status | Active | |
| tree | IEEE - The Institute of Electrical and Electronics Engineers, Inc.:;2006 | |
| contenttype | fulltext |