description abstractAbstract:
When single-phase power is pulled from a 3-phase supply (e.g., for Orbiter lighting) that is feeding critical 3-phase motors, there is a resulting phase imbalance (especially neutral leg current) that can disrupt instrumentation that is monitoring the health of other equipment. This instrumentation monitors the current draw of the motor (or an associated load such as a fluid pump) to sense motor loading that may indicate when a bearing is wearing out, a pump is stalling, or there are short or open circuits. Whenever possible, dedicated 3-phase power should be provided to critical rotary equipment to alleviate this problem.
languageEnglish
titleNASA-LLIS-4057num
titleLessons Learned - Spacecraft Single Phase AC Electrical Powerlantsen
typestandard
page3
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;2011
contenttypefulltext
subject keywordsCrew Survival Systems
subject keywordsEngineering design and project processes and standards
subject keywordsLander Systems
subject keywordsLevel II/III requirements definition
subject keywordsMission and systems trade studies
subject keywordsOrbiting Vehicles
subject keywordsReliability
subject keywordsTest & Verification
subject keywordsVehicle concepts


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record