Show simple item record

Lessons Learned - High Voltage Electric Circuits

contributor authorNASA - National Aeronautics and Space Administration (NASA)
date accessioned2017-09-04T15:43:46Z
date available2017-09-04T15:43:46Z
date copyright33924
date issued1992
identifier otherPNBEQCAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/46059
description abstractDescription of Driving Event:
During the removal of power to a transformer prior to it being serviced, an accidental 2400 Volt line to ground short circuit was created resulting in minor injury to a technician and minor hardware damage. The major contributing factor to this mishap was the use of a drawing that was not adequately checked after additions and changes had been made to the system. The secondary factor was that the technician did not test the voltage on the line side of the potential transformer compartment to verify that the bus was in fact de-energized.
languageEnglish
titleNASA-LLIS-0443num
titleLessons Learned - High Voltage Electric Circuitsen
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1992
contenttypefulltext
subject keywordsConfiguration Management
subject keywordsEnergy
subject keywordsLogistics
subject keywordsSafety & Mission Assurance


Files in this item

Thumbnail

This item appears in the following Collection(s)