description abstractDescription of Driving Event:
While installing electrical cables into a conduit in the Johnson Space Center Mission Control Room, the conduit was displaced from its mounting, and then contacted and broke a chilled water line. A portion of the room was flooded. The installation procedures did not include details for using sufficient lubrication on the cables being pulled through the conduit. Also, no cautions or warnings were provided to alert the electricians to take additional precautions to prevent accidents in a high value, mission essential area. Other factors that increased the extent of damage included; (1) an emergency plan that did not include water leaks, and (2) no information was available to the maintenance or operations personnel on the location of or access to shutoff systems. The investigation board recommended correcting the deficiencies in the work procedures, emergency plans, and mission control allowable work.
languageEnglish
titleNASA-LLIS-0003num
titleLessons Learned - Hazard Potentials Associated With Maintenance in High Valued, Mission Critical Areas (Mission Control at JSC)en
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1991
contenttypefulltext
subject keywordsConfiguration Management
subject keywordsEmergency Preparedness
subject keywordsFacilities
subject keywordsGround Equipment
subject keywordsIndustrial Operations


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record