Recommended Practice for Partial Discharge Measurement in Liquid-Filled Power Transformers and Shunt Reactors

contributor authorIEEE - The Institute of Electrical and Electronics Engineers, Inc.
date accessioned2017-09-04T16:22:20Z
date available2017-09-04T16:22:20Z
date copyright06/17/2010
date issued2010
identifier otherTPSMDDAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/85695
description abstractThis recommended practice describes the test procedure for the detection and measurement by the wideband apparent charge method of partial discharges (PDs) occurring in liquid-filled power transformers and shunt reactors during dielectric tests, where applicable.
Purpose
PD measurements in transformers and shunt reactors should preferably be made on the basis of measurement of the apparent charge. Relevant measuring systems are classified as narrowband or wideband systems. Both systems are recognized and widely used. Without giving preference to one or the other, it is the object of this document to describe the wideband method. General principles of PD measurements, including the narrowband method, are covered in IEC 60270 and IEC 60076-3 [B71].1, 2
1 Information on references can be found in Clause 2.
2 The numbers in brackets correspond to those of the bibliography in Annex H.
languageEnglish
titleIEEE C57.113num
titleRecommended Practice for Partial Discharge Measurement in Liquid-Filled Power Transformers and Shunt Reactorsen
typestandard
page47
statusActive
treeIEEE - The Institute of Electrical and Electronics Engineers, Inc.:;2010
contenttypefulltext
subject keywordsapparent charge
subject keywordsIEEE C57.113
subject keywordspartial discharge (PD)
subject keywordspower transformer
subject keywordsshunt reactor
subject keywordswideband PD measurement