Show simple item record

Lessons Learned – Mishap At The Underground Air Storage Facility

contributor authorNASA - National Aeronautics and Space Administration (NASA)
date accessioned2017-09-04T16:24:14Z
date available2017-09-04T16:24:14Z
date copyright05/22/2000
date issued2000
identifier otherTUTEQCAAAAAAAAAA.pdf
identifier urihttps://yse.yabesh.ir/std/handle/yse/87588
description abstractDescription of Driving Event:
A casing in Cluster #1 of the Underground Air Storage Facility (UASF) ruptured releasing high pressure air (3000 psig) into the substrate at about 500 ft below the surface. Although, quick action by the crew isolated the UASF from the rest of the distribution system, the entire 5x106 SCF of air, stored in the UASF, was released through the rupture. The released air created a crater around the affected cluster and sprayed mud onto the surrounding area for a radius of approximately 150 feet. Damage was localized to the one cluster. However, personnel that had entered the area to attempt to isolate the individual clusters from the manifold were exposed to streams of water and mud when evacuating the area.
languageEnglish
titleNASA-LLIS-0868num
titleLessons Learned – Mishap At The Underground Air Storage Facilityen
typestandard
page3
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;2000
contenttypefulltext
subject keywordsAdministration/Organization
subject keywordsEnergy
subject keywordsGround Equipment
subject keywordsHardware
subject keywordsPressure Vessels
subject keywordsTest & Verification
subject keywordsTest Facility