description abstractDescription of Driving Event:
The 540A industrial oxygen analyzer continuously monitors the oxygen content from samples of atmosphere. Monitored areas include the orbiter processing facility, vertical assembly building, mobile launch platform, and the pads. When the oxygen level in these areas drops to an unsafe level of 19.5% or less, an audible/visible alarm is activated to warn personnel to evacuate the area. The oxygen analyzer has a sensing circuit which relays data to a supervisory box assembly which triggers the battery box assembly if an oxygen deficiency is detected. The battery box assembly supplies power to the warning beacon and sends a read out to the complex center console C-2 (in the launch control center). A component failure within the oxygen analyzer due to fatigue/shorting may cause an erroneous high output signal when the oxygen level is below 19.5%, resulting in no alarm warning. Personnel may enter/work in the area, unaware of the low oxygen level, and become asphyxiated.
languageEnglish
titleNASA-LLIS-0142num
titleLessons Learned - 540A Industrial Oxygen (O2) Analyzer Monitoringen
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1992
contenttypefulltext
subject keywordsFacilities
subject keywordsGround Operations
subject keywordsLogistics
subject keywordsOccupational Health
subject keywordsRisk Management/Assessment


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record