Performance Requirements for Backflow Preventers with an Intermediate Atmospheric Vent - ANSI Approved: September 2009

contributor authorASSE - American Society of Sanitary Engineering
date accessioned2017-09-04T15:44:23Z
date available2017-09-04T15:44:23Z
date copyright03/11/2009
date issued2009
identifier otherPOWWOCAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std/handle/yse/46733
description abstractDescription
The devices covered by this standard are those which have functional capabilities for preventing both back-siphonage and back pressure and which can operate under continuous or intermittent pressure conditions. These devices have two (2) independently operating check valves separated by an intermediate chamber with a means for automatically venting it to the atmosphere and can be installed in the horizontal, vertical up or vertical down orientations. The check valves are force loaded to a normally closed position and the venting means is force loaded to a normally open position.
Size Range
Inlet and outlet pipe sizes are 1/4 to 3/4 NPS (8 mm to 20 mm) inclusive.
Minimum Pressure Rating
The device shall be designed and constructed for a working pressure of at least 150.0 psi (1034.2 kPa).
Temperature Range
The device shall be designed and constructed for normal flow temperatures of 40.0 °F to 210.0 °F (4.4 °C to 98.9 °C) and an emergency back pressure temperature of 250.0 °F (121.1 °C).
Flow Rate
Manufacturer's advertised maximum flow rate.
languageEnglish
titleASSE 1012num
titlePerformance Requirements for Backflow Preventers with an Intermediate Atmospheric Vent - ANSI Approved: September 2009en
typestandard
page24
statusActive
treeASSE - American Society of Sanitary Engineering:;2009
contenttypefulltext