ASHRAE 170 ADD A
Ventilation of Health Care Facilities
Year: 2009
Abstract: FOREWORD
The changes in this addendum clear up inconsistencies regarding design parameters for spaces. The following discusses the specific changes implemented in this addendum.
1. Modifications to Table 7-1, Design Parameters, for "Newborn intensive care." This change modifies the table entry for "Newborn intensive care" under the Design Temperature column to be the same as the Table entry for "Newborn nursery suite." These two spaces have similar design temperature requirements.
2. Modifications to Table 7-1, Design Parameters, for "Corridor." This change modifies the table entry for "Corridor" under the Function of Space column. This modification differentiates the requirements for minimum total air changes per hour in patient corridors from those corridors within health care facilities in which patients are not present.
3. Modifications to Table 7-1, footnote k. This change modifies the footnote to denote that some entries have only a maximum relative humidity requirement. This change also deletes the word "control" and its associated interpretations from the text and replaces it with new text.
4. Modifications to Table 7-1, footnote n. This change modifies the footnote to denote which type of "monitoring device alarms" is the subject of the sentence since the footnote discusses a variety of topics.
The changes in this addendum clear up inconsistencies regarding design parameters for spaces. The following discusses the specific changes implemented in this addendum.
1. Modifications to Table 7-1, Design Parameters, for "Newborn intensive care." This change modifies the table entry for "Newborn intensive care" under the Design Temperature column to be the same as the Table entry for "Newborn nursery suite." These two spaces have similar design temperature requirements.
2. Modifications to Table 7-1, Design Parameters, for "Corridor." This change modifies the table entry for "Corridor" under the Function of Space column. This modification differentiates the requirements for minimum total air changes per hour in patient corridors from those corridors within health care facilities in which patients are not present.
3. Modifications to Table 7-1, footnote k. This change modifies the footnote to denote that some entries have only a maximum relative humidity requirement. This change also deletes the word "control" and its associated interpretations from the text and replaces it with new text.
4. Modifications to Table 7-1, footnote n. This change modifies the footnote to denote which type of "monitoring device alarms" is the subject of the sentence since the footnote discusses a variety of topics.
-
Statistics
ASHRAE 170 ADD A
Show full item record
contributor author | ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. | |
date accessioned | 2017-09-04T18:47:45Z | |
date available | 2017-09-04T18:47:45Z | |
date copyright | 06/20/2009 | |
date issued | 2009 | |
identifier other | KMZUMCAAAAAAAAAA.pdf | |
identifier uri | http://yse.yabesh.ir/std;jsessionid=435F2D89F77216F55ECC40BAF539160F/handle/yse/228999 | |
description abstract | FOREWORD The changes in this addendum clear up inconsistencies regarding design parameters for spaces. The following discusses the specific changes implemented in this addendum. 1. Modifications to Table 7-1, Design Parameters, for "Newborn intensive care." This change modifies the table entry for "Newborn intensive care" under the Design Temperature column to be the same as the Table entry for "Newborn nursery suite." These two spaces have similar design temperature requirements. 2. Modifications to Table 7-1, Design Parameters, for "Corridor." This change modifies the table entry for "Corridor" under the Function of Space column. This modification differentiates the requirements for minimum total air changes per hour in patient corridors from those corridors within health care facilities in which patients are not present. 3. Modifications to Table 7-1, footnote k. This change modifies the footnote to denote that some entries have only a maximum relative humidity requirement. This change also deletes the word "control" and its associated interpretations from the text and replaces it with new text. 4. Modifications to Table 7-1, footnote n. This change modifies the footnote to denote which type of "monitoring device alarms" is the subject of the sentence since the footnote discusses a variety of topics. | |
language | English | |
title | ASHRAE 170 ADD A | num |
title | Ventilation of Health Care Facilities | en |
type | standard | |
page | 4 | |
status | Revised | |
tree | ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2009 | |
contenttype | fulltext |