Ventilation of Health Care Facilities

ASHRAE 170 INT 4

Organization:
ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
Year: 2019

Abstract: A return air, variable air volume air handling system contains an air handling unit (AHU) equipped with an airside economizer. (2 ACH)(200)(9)/60 = 60 cfm of outdoor air minimum is required in each patient room. The AHU is designed to be controlled to always bring in a minimum of (60 cfm OA)(50 patient rooms) = 3,000 cfm of outdoor air. Paragraph 7.1.a.6 allows the use of method 7.1.a.6.i whereby: “i. System minimum outdoor air quantity for an air-handling system shall be calculated as the sum of the individual space requirements as defined by the standard.” Topics outdoor air;outdoor air cfm;background ahu;outdoor air cfm minimum;outdoor air minimum cfm
URI: http://yse.yabesh.ir/std;query=autho162/handle/yse/280384
Collections :
  • ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
  • Download PDF : (124.1Kb)
  • Show Full MetaData Hide Full MetaData
  • Statistics

    Ventilation of Health Care Facilities

Show full item record

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2020-07-27T20:51:04Z
date available2020-07-27T20:51:04Z
date issued2019
identifier otherNRYBJGAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;query=autho162/handle/yse/280384
description abstractA return air, variable air volume air handling system contains an air handling unit (AHU) equipped with an airside economizer. (2 ACH)(200)(9)/60 = 60 cfm of outdoor air minimum is required in each patient room. The AHU is designed to be controlled to always bring in a minimum of (60 cfm OA)(50 patient rooms) = 3,000 cfm of outdoor air. Paragraph 7.1.a.6 allows the use of method 7.1.a.6.i whereby: “i. System minimum outdoor air quantity for an air-handling system shall be calculated as the sum of the individual space requirements as defined by the standard.” Topics outdoor air;outdoor air cfm;background ahu;outdoor air cfm minimum;outdoor air minimum cfm
languageEnglish
titleVentilation of Health Care Facilitiesen
titleASHRAE 170 INT 4num
typestandard
page4
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2019
contenttypefulltext
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian
 
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian