ASHRAE LO-09-027

Required Duration For Borehole Test Validated by Field Data

Organization:
ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
Year: 2009

Abstract: ABSTRACT
Geothermal heat pumps exchange heat with the ground through the use of ground heat exchangers where the heat transfer rate depends on the thermal conductivity of the surrounding soil. An in-situ test is often performed on a vertical borehole to estimate soil thermal conductivity, but the test must have sufficient duration in order to obtain an accurate estimate. Conventional analysis methods usually do not check to see if the test duration is sufficient. This paper validates a procedure to perform this check as a supplement to current methods. The procedure uses an analytical composite model of borehole heat transfer to estimate the minimum test duration necessary to determine soil thermal conductivity within 5% of the estimated value from a very long test. Data sets from 16 field tests are used in the validation process. The minimum test duration ranges from approximately 10 to 53 hours among the tests when a simplified line-source model is used for evaluating soil thermal conductivity. The results indicate no simple rule for minimum duration applies to all cases. Instead, the proposed procedure based on the analytical composite model can determine if test duration is sufficient.
URI: http://yse.yabesh.ir/std;query=autho162sear79D/handle/yse/220674
Collections :
  • ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
  • Download PDF : (640.4Kb)
  • Show Full MetaData Hide Full MetaData
  • Statistics

    ASHRAE LO-09-027

Show full item record

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2017-09-04T18:39:01Z
date available2017-09-04T18:39:01Z
date copyright01/01/2009
date issued2009
identifier otherJQYXPCAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;query=autho162sear79D/handle/yse/220674
description abstractABSTRACT
Geothermal heat pumps exchange heat with the ground through the use of ground heat exchangers where the heat transfer rate depends on the thermal conductivity of the surrounding soil. An in-situ test is often performed on a vertical borehole to estimate soil thermal conductivity, but the test must have sufficient duration in order to obtain an accurate estimate. Conventional analysis methods usually do not check to see if the test duration is sufficient. This paper validates a procedure to perform this check as a supplement to current methods. The procedure uses an analytical composite model of borehole heat transfer to estimate the minimum test duration necessary to determine soil thermal conductivity within 5% of the estimated value from a very long test. Data sets from 16 field tests are used in the validation process. The minimum test duration ranges from approximately 10 to 53 hours among the tests when a simplified line-source model is used for evaluating soil thermal conductivity. The results indicate no simple rule for minimum duration applies to all cases. Instead, the proposed procedure based on the analytical composite model can determine if test duration is sufficient.
languageEnglish
titleASHRAE LO-09-027num
titleRequired Duration For Borehole Test Validated by Field Dataen
typestandard
page11
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2009
contenttypefulltext
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian
 
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian