BACnet - A Data Communication Protocol for Building Automation and Control Networks
ASHRAE 135 INT 24
Year: 2020
Abstract: Duffy O'Craven, 1600 Beacon St. #806 Brookline, MA 02446
This request for interpretation refers to the requirements presented in ANSI/ASHRAE Standard 135-2016, Clause 12.57, regarding writing when State_Change_Values intends to relinquish on all transitions from RUNNING.
Numerous transitions in the Timer object are designed to give detailed control in the situation when a Timer is utilized to command a property for a timed period.
The language implies that execution of DeleteObject is asynchronously supported, even if performed while the Timer is RUNNING, but there is no language that explicitly states what State_Change_Values information is used to accomplish this case.
-
Statistics
BACnet - A Data Communication Protocol for Building Automation and Control Networks
Show full item record
| contributor author | ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. | |
| date accessioned | 2020-08-03T12:00:00Z | |
| date available | 2020-08-03T12:00:00Z | |
| date issued | 2020 | |
| identifier other | LKPDMGAAAAAAAAAA.pdf | |
| identifier uri | http://yse.yabesh.ir/std;query=autho47037D83FCDCAC426159DD6E273C9FCD/handle/yse/280691 | |
| description abstract | Duffy O'Craven, 1600 Beacon St. #806 Brookline, MA 02446 This request for interpretation refers to the requirements presented in ANSI/ASHRAE Standard 135-2016, Clause 12.57, regarding writing when State_Change_Values intends to relinquish on all transitions from RUNNING. Numerous transitions in the Timer object are designed to give detailed control in the situation when a Timer is utilized to command a property for a timed period. The language implies that execution of DeleteObject is asynchronously supported, even if performed while the Timer is RUNNING, but there is no language that explicitly states what State_Change_Values information is used to accomplish this case. | |
| language | English | |
| title | BACnet - A Data Communication Protocol for Building Automation and Control Networks | en |