Archive

BACnet - A Data Communication Protocol for Building Automation and Control Networks

ASHRAE 135 INT 20

Organization:
ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
Year: 2019

Abstract: Chris Howard, Schneider Electric. 800 Federal Street, Andover, Massachusetts. This request for interpretation refers to the requirements presented in ANSI/ASHRAE Standard 135-2016, Clauses 5.2.1.2, 9.7.1 and 19.4, regarding the requirements for devices to know the Maximum Conveyable APDU to remote networks Clause 19.4 outlines a procedure for a 'node' to determine the Maximum Conveyable APDU to a remote network and requires the node to cache the determined value. References in the Standard that refer to Clause 19.4 are found in Clause 5.2 (Segmentation) and 9.7.1 (Routing of BACnet Messages from MS/TP). There are some inconsistencies in Clause 5.2.1.2 because Clause 5.2.1.2 (b) implies that a device must know the maximum APDU size conveyable to a remote network to choose an appropriate APDU size that will reach the recipient
URI: http://yse.yabesh.ir/std;query=autho47037D83FCDCAC426159DD6E273C9FCD/handle/yse/280717
Collections :
  • ASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
  • Download PDF : (34.08Kb)
  • Show Full MetaData Hide Full MetaData
  • Statistics

    BACnet - A Data Communication Protocol for Building Automation and Control Networks

Show full item record

contributor authorASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.
date accessioned2020-08-03T12:00:07Z
date available2020-08-03T12:00:07Z
date issued2019
identifier otherZVZLKGAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std;query=autho47037D83FCDCAC426159DD6E273C9FCD/handle/yse/280717
description abstractChris Howard, Schneider Electric. 800 Federal Street, Andover, Massachusetts. This request for interpretation refers to the requirements presented in ANSI/ASHRAE Standard 135-2016, Clauses 5.2.1.2, 9.7.1 and 19.4, regarding the requirements for devices to know the Maximum Conveyable APDU to remote networks Clause 19.4 outlines a procedure for a 'node' to determine the Maximum Conveyable APDU to a remote network and requires the node to cache the determined value. References in the Standard that refer to Clause 19.4 are found in Clause 5.2 (Segmentation) and 9.7.1 (Routing of BACnet Messages from MS/TP). There are some inconsistencies in Clause 5.2.1.2 because Clause 5.2.1.2 (b) implies that a device must know the maximum APDU size conveyable to a remote network to choose an appropriate APDU size that will reach the recipient
languageEnglish
titleBACnet - A Data Communication Protocol for Building Automation and Control Networksen
titleASHRAE 135 INT 20num
typestandard
page2
statusActive
treeASHRAE - American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc.:;2019
contenttypefulltext
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian
 
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian