IEEE C57.13.6
Standard for High-Accuracy Instrument Transformers
Year: 2005
Abstract: This standard defines one new 0.15 accuracy class for voltage transformers, two new 0.15 accuracy classes for current transformers, two new current transformer burdens, and two new current transformer routine accuracy test methods. These supplement IEEE Std C57.13™1. The new burdens shall be considered for use when current transformers are to be used with electronic meters, and the total in-circuit burden will be less than B-0.1 (2.5 VA at 5 A, 0.9 power factor) defined in IEEE Std C57.13. The new accuracy classes, 0.15 and 0.15S, are available to complement the capabilities of solid state electricity metering of equipment associated with the generation, transmission, and distribution of alternating current.
There are two important differences about these new accuracy class definitions as they apply to routine current transformer test requirements:
a) A low current test is required at 5% of rated current (0.25 A secondary), in lieu of the 10% of rated current test specified in IEEE Std C57.13. This test point corresponds with the light load test point of transformer rated electromechanical and solid state electricity meters as specified in ANSI C12.20.
b) Routine testing for current transformers certified to meet 0.15 or 0.15S accuracy must include accuracy reading(s) using new burden definition E-0.04. The intent of burden E-0.04 (1.0 VA at 5 A, unity power factor) is to approximate the lowest secondary circuit burden that can occur in practical applications. Testing a current transformer at this burden is analogous to the routine no-load voltage transformer test required by IEEE Std C57.13.
1 Information on references can be found in Clause 2.
There are two important differences about these new accuracy class definitions as they apply to routine current transformer test requirements:
a) A low current test is required at 5% of rated current (0.25 A secondary), in lieu of the 10% of rated current test specified in IEEE Std C57.13. This test point corresponds with the light load test point of transformer rated electromechanical and solid state electricity meters as specified in ANSI C12.20.
b) Routine testing for current transformers certified to meet 0.15 or 0.15S accuracy must include accuracy reading(s) using new burden definition E-0.04. The intent of burden E-0.04 (1.0 VA at 5 A, unity power factor) is to approximate the lowest secondary circuit burden that can occur in practical applications. Testing a current transformer at this burden is analogous to the routine no-load voltage transformer test required by IEEE Std C57.13.
1 Information on references can be found in Clause 2.
Subject: accuracy class
Show full item record
| contributor author | IEEE - The Institute of Electrical and Electronics Engineers, Inc. | |
| date accessioned | 2017-09-04T17:57:22Z | |
| date available | 2017-09-04T17:57:22Z | |
| date copyright | 09/22/2005 | |
| date issued | 2005 | |
| identifier other | FONSIBAAAAAAAAAA.pdf | |
| identifier uri | https://yse.yabesh.ir/std/handle/yse/180444 | |
| description abstract | This standard defines one new 0.15 accuracy class for voltage transformers, two new 0.15 accuracy classes for current transformers, two new current transformer burdens, and two new current transformer routine accuracy test methods. These supplement IEEE Std C57.13™1. The new burdens shall be considered for use when current transformers are to be used with electronic meters, and the total in-circuit burden will be less than B-0.1 (2.5 VA at 5 A, 0.9 power factor) defined in IEEE Std C57.13. The new accuracy classes, 0.15 and 0.15S, are available to complement the capabilities of solid state electricity metering of equipment associated with the generation, transmission, and distribution of alternating current. There are two important differences about these new accuracy class definitions as they apply to routine current transformer test requirements: a) A low current test is required at 5% of rated current (0.25 A secondary), in lieu of the 10% of rated current test specified in IEEE Std C57.13. This test point corresponds with the light load test point of transformer rated electromechanical and solid state electricity meters as specified in ANSI C12.20. b) Routine testing for current transformers certified to meet 0.15 or 0.15S accuracy must include accuracy reading(s) using new burden definition E-0.04. The intent of burden E-0.04 (1.0 VA at 5 A, unity power factor) is to approximate the lowest secondary circuit burden that can occur in practical applications. Testing a current transformer at this burden is analogous to the routine no-load voltage transformer test required by IEEE Std C57.13. 1 Information on references can be found in Clause 2. | |
| language | English | |
| title | IEEE C57.13.6 | num |
| title | Standard for High-Accuracy Instrument Transformers | en |
| type | standard | |
| page | 16 | |
| status | Active | |
| tree | IEEE - The Institute of Electrical and Electronics Engineers, Inc.:;2005 | |
| contenttype | fulltext | |
| subject keywords | accuracy class | |
| subject keywords | burden | |
| subject keywords | CT | |
| subject keywords | current transformer | |
| subject keywords | high-accuracy | |
| subject keywords | instrument transformer | |
| subject keywords | metering | |
| subject keywords | meters | |
| subject keywords | phase angle | |
| subject keywords | PT | |
| subject keywords | ratio correction factor | |
| subject keywords | RCF | |
| subject keywords | relays | |
| subject keywords | revenue metering | |
| subject keywords | TCF | |
| subject keywords | transformer correction factor | |
| subject keywords | voltage transformer | |
| subject keywords | VT |