NASA-LLIS-0299

Lessons Learned - Dry Well Transducer Installations are Susceptial to Inadvertent Removal

Organization:
NASA - National Aeronautics and Space Administration (NASA)
Year: 1993

Abstract: Description of Driving Event:
A Hypergol technician erred in the removal of a temperature transducer from a 3-inch Hypergol line at the pad "A" fuel farm, resulting in a major fuel spill. The installation design of the dry well and temperature transducer provide a means to remove the transducer from the system for replacement or calibration without having to open the fluid volume. The dry well installation design is inadequate to preclude an untrained or careless technician from inadvertently removing the dry well from the Hypergol propellant line by mistake.
Additional Comments:
OMI V2196 Titled: "Hyper Fuel System Validation Storage Area-Local Control/LPS" has been updated to include the following warning: "Removing transducers from dry wells may be hazardous. A restaining retainer is designed to prevent removal of dry well while secured in place by set screws. As transducers are being removed from dry wells, PMTG shall visually verify that dry wells are not turning. Wear face shield, apron and rubber gloves and use extreme care to avoid inadvertent loosening of any temperature XDCR dry well, which could release MMH liquid. If A78633 TEMP XDCR dry well is loosened the entire storage tank contents could be released."
URI: http://yse.yabesh.ir/std/handle/yse/142884
Subject: Energetic Materials - Explosive/Propellant/Pyrotechnic
Collections :
  • NASA - National Aeronautics and Space Administration (NASA)
  • Download PDF : (13.50Kb)
  • Show Full MetaData Hide Full MetaData
  • Statistics

    NASA-LLIS-0299

Show full item record

contributor authorNASA - National Aeronautics and Space Administration (NASA)
date accessioned2017-09-04T17:19:39Z
date available2017-09-04T17:19:39Z
date copyright08/18/1993
date issued1993
identifier otherZNZCQCAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std/handle/yse/142884
description abstractDescription of Driving Event:
A Hypergol technician erred in the removal of a temperature transducer from a 3-inch Hypergol line at the pad "A" fuel farm, resulting in a major fuel spill. The installation design of the dry well and temperature transducer provide a means to remove the transducer from the system for replacement or calibration without having to open the fluid volume. The dry well installation design is inadequate to preclude an untrained or careless technician from inadvertently removing the dry well from the Hypergol propellant line by mistake.
Additional Comments:
OMI V2196 Titled: "Hyper Fuel System Validation Storage Area-Local Control/LPS" has been updated to include the following warning: "Removing transducers from dry wells may be hazardous. A restaining retainer is designed to prevent removal of dry well while secured in place by set screws. As transducers are being removed from dry wells, PMTG shall visually verify that dry wells are not turning. Wear face shield, apron and rubber gloves and use extreme care to avoid inadvertent loosening of any temperature XDCR dry well, which could release MMH liquid. If A78633 TEMP XDCR dry well is loosened the entire storage tank contents could be released."
languageEnglish
titleNASA-LLIS-0299num
titleLessons Learned - Dry Well Transducer Installations are Susceptial to Inadvertent Removalen
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1993
contenttypefulltext
subject keywordsEnergetic Materials - Explosive/Propellant/Pyrotechnic
subject keywordsFacilities
subject keywordsHazardous/Toxic Waste/Materials