Lessons Learned – Improper Facility Planning and Utilization

Organization:
NASA - National Aeronautics and Space Administration (NASA)
Year: 1997

Abstract: Description of Driving Event:
Due to overall dwindling budgets and severe cutbacks in operational budgets, onsite space is being used whenever possible to house personnel and operations to avoid renting offsite space. In this instance, personnel were located in sections of two buildings designed for main frame type computers. People began to complain about headaches and other ailments as well as the conditioning of the air in these locations. Carbon dioxide concentrations in these areas were evaluated and found to exceed the 1000 ppm recommended by the American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc. (ASHRAE). ASHRAE 62-1989, "Ventilation for Acceptable Indoor Air Quality". Carbon dioxide concentrations exceeding 1000 ppm indicate insufficient make-up air and the possibility of build up of other indoor contaminants.
URI: http://yse.yabesh.ir/std/handle/yse/165248
Subject: Facilities
Collections :
  • NASA - National Aeronautics and Space Administration (NASA)
  • Download PDF : (13.29Kb)
  • Show Full MetaData Hide Full MetaData
  • Statistics

    NASA-LLIS-0532

Show full item record

contributor authorNASA - National Aeronautics and Space Administration (NASA)
date accessioned2017-09-04T17:42:14Z
date available2017-09-04T17:42:14Z
date copyright03/21/1997
date issued1997
identifier otherEACEQCAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std/handle/yse/165248
description abstractDescription of Driving Event:
Due to overall dwindling budgets and severe cutbacks in operational budgets, onsite space is being used whenever possible to house personnel and operations to avoid renting offsite space. In this instance, personnel were located in sections of two buildings designed for main frame type computers. People began to complain about headaches and other ailments as well as the conditioning of the air in these locations. Carbon dioxide concentrations in these areas were evaluated and found to exceed the 1000 ppm recommended by the American Society of Heating, Refrigerating, and Air Conditioning Engineers, Inc. (ASHRAE). ASHRAE 62-1989, "Ventilation for Acceptable Indoor Air Quality". Carbon dioxide concentrations exceeding 1000 ppm indicate insufficient make-up air and the possibility of build up of other indoor contaminants.
languageEnglish
titleNASA-LLIS-0532num
titleLessons Learned – Improper Facility Planning and Utilizationen
typestandard
page2
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1997
contenttypefulltext
subject keywordsFacilities
subject keywordsOccupational Health