NASA-LLIS-1183

Lessons Learned - Orbiter Processing Facility Bay 2 Water Deluge System Flow Mishap Investigation Board Report of October 25, 1989

Organization:
NASA - National Aeronautics and Space Administration (NASA)
Year: 1989

Abstract: Description of Driving Event:
The Orbiter Processing Facility (OPF) Bay 2 Firex Deluge Zone 3 Viking arm valve AV1.3-2 was leaking, and on September 21, 1989, Problem Report (PR) number PV-6-140247 was initiated to replace defective parts. During system leak check operations following valve repair, water flow from zone 3 (directly over the Orbiter) occurred in OPF Bay 2. The time of first flow was established as 10:28 AM on September 24, 1989, as recorded by OPF Water Pump House instrumentation due to diesel pump startup. The Zone 3 water flow over the Orbiter was at a reduced rate, with only a partial nozzle discharge pattern.
Shuttle Processing Contract (SPC) Water Systems technicians were cycling the manual arming and firing valves while leak checking the system. Only a few minutes had passed from the time they cracked open (2 turns) the system manual supply valve until they heard about the water flow problem in Bay 2. The SPC Lead Water Systems technician ran into the OPF to see what was wrong and noted the deluge flow. He returned to the manual activation station behind the OPF and found that two SPC ground support equipment (GSE) technicians had opened the manual arming and firing valve to Zones 1, 2, 3, 4, and 5. (It is presumed Zone 3 did not flow additional water and had been deactivated by this time.) The Lead Water Systems technician then closed all the open manual arming and firing valves, as well as the manual supply isolation valves to stop all Bay 2 water flow.
The scenario that lead to the two GSE technicians being at the deluge system manual flow control valve station is as follows:
After the flow from Zone 3 occurred, the SPC OPF Bay 1 Site Division Manager asked a GSE technician to find someone who could turn the system off. This GSE technician, accompanied by a co-worker, proceeded to the manual activation station behind Bay 2. Upon arrival, they proceeded to position the manual arming and firing valves to Zones 1, 2, 3, 4, and 5 to the "on" position, thinking they were turning the firex system off. This turned on deluge system Zones 1, 2, 4, and 5 (Zone 3 had already been deactivated) to the "full on" mode. The Lead Water Systems technician then returned to the manual valve panels, proceeded to turn the manual arming and firing valves to the "off" position, and then helped his technicians close the manual supply isolation valves to Zones 1 through 5, which stopped all water flow.
URI: http://yse.yabesh.ir/std/handle/yse/175963
Subject: Emergency Preparedness
Collections :
  • NASA - National Aeronautics and Space Administration (NASA)
  • Download PDF : (18.51Kb)
  • Show Full MetaData Hide Full MetaData
  • Statistics

    NASA-LLIS-1183

Show full item record

contributor authorNASA - National Aeronautics and Space Administration (NASA)
date accessioned2017-09-04T17:52:49Z
date available2017-09-04T17:52:49Z
date copyright32806
date issued1989
identifier otherFCVEQCAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std/handle/yse/175963
description abstractDescription of Driving Event:
The Orbiter Processing Facility (OPF) Bay 2 Firex Deluge Zone 3 Viking arm valve AV1.3-2 was leaking, and on September 21, 1989, Problem Report (PR) number PV-6-140247 was initiated to replace defective parts. During system leak check operations following valve repair, water flow from zone 3 (directly over the Orbiter) occurred in OPF Bay 2. The time of first flow was established as 10:28 AM on September 24, 1989, as recorded by OPF Water Pump House instrumentation due to diesel pump startup. The Zone 3 water flow over the Orbiter was at a reduced rate, with only a partial nozzle discharge pattern.
Shuttle Processing Contract (SPC) Water Systems technicians were cycling the manual arming and firing valves while leak checking the system. Only a few minutes had passed from the time they cracked open (2 turns) the system manual supply valve until they heard about the water flow problem in Bay 2. The SPC Lead Water Systems technician ran into the OPF to see what was wrong and noted the deluge flow. He returned to the manual activation station behind the OPF and found that two SPC ground support equipment (GSE) technicians had opened the manual arming and firing valve to Zones 1, 2, 3, 4, and 5. (It is presumed Zone 3 did not flow additional water and had been deactivated by this time.) The Lead Water Systems technician then closed all the open manual arming and firing valves, as well as the manual supply isolation valves to stop all Bay 2 water flow.
The scenario that lead to the two GSE technicians being at the deluge system manual flow control valve station is as follows:
After the flow from Zone 3 occurred, the SPC OPF Bay 1 Site Division Manager asked a GSE technician to find someone who could turn the system off. This GSE technician, accompanied by a co-worker, proceeded to the manual activation station behind Bay 2. Upon arrival, they proceeded to position the manual arming and firing valves to Zones 1, 2, 3, 4, and 5 to the "on" position, thinking they were turning the firex system off. This turned on deluge system Zones 1, 2, 4, and 5 (Zone 3 had already been deactivated) to the "full on" mode. The Lead Water Systems technician then returned to the manual valve panels, proceeded to turn the manual arming and firing valves to the "off" position, and then helped his technicians close the manual supply isolation valves to Zones 1 through 5, which stopped all water flow.
languageEnglish
titleNASA-LLIS-1183num
titleLessons Learned - Orbiter Processing Facility Bay 2 Water Deluge System Flow Mishap Investigation Board Report of October 25, 1989en
typestandard
page4
statusActive
treeNASA - National Aeronautics and Space Administration (NASA):;1989
contenttypefulltext
subject keywordsEmergency Preparedness
subject keywordsFacilities
subject keywordsFire Protection
subject keywordsGround Equipment
subject keywordsGround Operations
subject keywordsHardware
subject keywordsHuman Factors
subject keywordsLogistics
subject keywordsMishap Reporting