UL 1053 BULLETIN
UL Standard for Safety Ground-Fault Sensing and Relaying Equipment - COMMENTS DUE: November 17, 2008
Organization:
UL - UL
Year: 2008
Abstract: These requirements cover ground-fault current sensing devices, relaying equipment, or combinations of ground-fault current sensing devices and relaying equipment or equivalent protection equipment for use in ordinary locations that will operate to cause a disconnecting device to open all ungrounded conductors at predetermined values of ground-fault current, in accordance with the National Electrical Code, ANSI/NFPA 70.
These requirements cover equipment intended for use in circuits that are solidly grounded and that operate at 150 volts, or more, to ground, but not more than 600 volts phase-to-phase.
1.2 revised and separated into 1.3 and 1.4 October 27, 1999
These requirements do not cover equipment intended to be powered from circuits operating at more than 600 volts.
1.3 relocated from 1.2 October 27, 1999
These requirements do not cover ground-fault circuit-interrupters.
1.4 relocated from 1.2 October 27, 1999
These devices are intended to operate with shunt-trip circuit breakers, electrically tripped bolted pressure contact switches and the like that constitute the disconnecting means.
1.6 A Class I ground-fault protection device is one that does not incorporate means to prevent opening of the disconnecting means at high levels of fault current and is intended for use with the following:
a) Circuit breakers,
b) Fused circuit breakers,
c) Fused switches having an interrupting rating not less than 12 times their ampere rating, or
d) Fused switches having integral means to prevent disconnecting at levels of fault current exceeding the contact interrupting rating of the switch.
A Class II ground-fault protection device is one that incorporates means to prevent initiation of opening of the disconnecting device if the fault current exceeds the contact interrupting capability of the disconnecting device with which it is intended to be used.
These requirements cover enclosed-type devices and also cover open-type devices that are intended for use in other equipment, such as panelboards, switchboards, and the like.
A product that contains features, characteristics, components, materials, or systems new or different from those covered by the requirements in this Standard, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end-product requirements to determine that the level of safety as originally anticipated by the intent of this Standard is maintained. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this Standard shall not be judged to comply with this Standard. Where appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revision, and implementation of this Standard.
These requirements cover equipment intended for use in circuits that are solidly grounded and that operate at 150 volts, or more, to ground, but not more than 600 volts phase-to-phase.
1.2 revised and separated into 1.3 and 1.4 October 27, 1999
These requirements do not cover equipment intended to be powered from circuits operating at more than 600 volts.
1.3 relocated from 1.2 October 27, 1999
These requirements do not cover ground-fault circuit-interrupters.
1.4 relocated from 1.2 October 27, 1999
These devices are intended to operate with shunt-trip circuit breakers, electrically tripped bolted pressure contact switches and the like that constitute the disconnecting means.
1.6 A Class I ground-fault protection device is one that does not incorporate means to prevent opening of the disconnecting means at high levels of fault current and is intended for use with the following:
a) Circuit breakers,
b) Fused circuit breakers,
c) Fused switches having an interrupting rating not less than 12 times their ampere rating, or
d) Fused switches having integral means to prevent disconnecting at levels of fault current exceeding the contact interrupting rating of the switch.
A Class II ground-fault protection device is one that incorporates means to prevent initiation of opening of the disconnecting device if the fault current exceeds the contact interrupting capability of the disconnecting device with which it is intended to be used.
These requirements cover enclosed-type devices and also cover open-type devices that are intended for use in other equipment, such as panelboards, switchboards, and the like.
A product that contains features, characteristics, components, materials, or systems new or different from those covered by the requirements in this Standard, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end-product requirements to determine that the level of safety as originally anticipated by the intent of this Standard is maintained. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this Standard shall not be judged to comply with this Standard. Where appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revision, and implementation of this Standard.
Collections
:
-
Statistics
UL 1053 BULLETIN
Show full item record
| contributor author | UL - UL | |
| date accessioned | 2017-09-04T18:35:52Z | |
| date available | 2017-09-04T18:35:52Z | |
| date copyright | 39738 | |
| date issued | 2008 | |
| identifier other | JJSKHCAAAAAAAAAA.pdf | |
| identifier uri | http://yse.yabesh.ir/std/handle/yse/217833 | |
| description abstract | These requirements cover ground-fault current sensing devices, relaying equipment, or combinations of ground-fault current sensing devices and relaying equipment or equivalent protection equipment for use in ordinary locations that will operate to cause a disconnecting device to open all ungrounded conductors at predetermined values of ground-fault current, in accordance with the National Electrical Code, ANSI/NFPA 70. These requirements cover equipment intended for use in circuits that are solidly grounded and that operate at 150 volts, or more, to ground, but not more than 600 volts phase-to-phase. 1.2 revised and separated into 1.3 and 1.4 October 27, 1999 These requirements do not cover equipment intended to be powered from circuits operating at more than 600 volts. 1.3 relocated from 1.2 October 27, 1999 These requirements do not cover ground-fault circuit-interrupters. 1.4 relocated from 1.2 October 27, 1999 These devices are intended to operate with shunt-trip circuit breakers, electrically tripped bolted pressure contact switches and the like that constitute the disconnecting means. 1.6 A Class I ground-fault protection device is one that does not incorporate means to prevent opening of the disconnecting means at high levels of fault current and is intended for use with the following: a) Circuit breakers, b) Fused circuit breakers, c) Fused switches having an interrupting rating not less than 12 times their ampere rating, or d) Fused switches having integral means to prevent disconnecting at levels of fault current exceeding the contact interrupting rating of the switch. A Class II ground-fault protection device is one that incorporates means to prevent initiation of opening of the disconnecting device if the fault current exceeds the contact interrupting capability of the disconnecting device with which it is intended to be used. These requirements cover enclosed-type devices and also cover open-type devices that are intended for use in other equipment, such as panelboards, switchboards, and the like. A product that contains features, characteristics, components, materials, or systems new or different from those covered by the requirements in this Standard, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end-product requirements to determine that the level of safety as originally anticipated by the intent of this Standard is maintained. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this Standard shall not be judged to comply with this Standard. Where appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revision, and implementation of this Standard. | |
| language | English | |
| title | UL 1053 BULLETIN | num |
| title | UL Standard for Safety Ground-Fault Sensing and Relaying Equipment - COMMENTS DUE: November 17, 2008 | en |
| type | standard | |
| page | 4 | |
| status | Active | |
| tree | UL - UL:;2008 | |
| contenttype | fulltext |