UL 1479

UL Standard for Safety Fire Tests of Through-Penetration Firestops - Third Edition; Reprint with Revisions through and Including October 19, 2012

Organization:
UL - UL
Year: 2003

Abstract: These requirements cover through-penetration firestops of various materials and construction that are intended for use in openings in fire resistive wall or floor-ceiling assemblies, or both.
The method of testing through-penetration firestops as specified by these requirements consists of exposure of test samples to a fire of standard time and temperature and to an application of a hose stream. Ratings are then established on the basis of:
a) The length of time the firestop resists fire before the first development of through openings or flaming on the unexposed surface,
b) Acceptable limitation of thermal transmission, and
c) Acceptable performance under the application of the hose stream.
The method of testing also includes optional air leakage tests to determine the rate of air leakage through through-penetration firestop systems resulting from a specified air pressure difference applied across the surface of the systems.
The method of testing also includes optional water leakage tests to determine the ability of through-penetration firestop systems to resist the passage of water under a three foot pressure head. This method does not evaluate the ability of uncured firestop systems to resist such exposure.
Two ratings are established for each through-penetration firestop system: an F rating based upon flame occurrence on the unexposed side of the test sample and acceptable hose stream performance; and a T rating based on temperature rise and flame occurrence on the unexposed side of the test sample and acceptable hose stream performance.
An L rating may also be established for a through-penetration firestop system. The L rating is based on the amount of air leakage through the test sample.
An W rating may also be established for a through-penetration firestop system. The W rating is based on the water resistance of the test sample.
The method of testing through-penetration firestop systems containing piping systems for vented (drain, waste or vent) systems and closed (process or supply) systems is differentiated by the capping or non-capping of the piping systems on the unexposed side of the test assembly as described in 4.1.2.
Tests conducted in accordance with these requirements are intended to demonstrate the performance of through-penetration firestops during exposure to fire, but are not intended to determine acceptability of firestops for use after exposure to fire. These requirements do not cover the ampacity of conductors encased in through-penetration firestop materials.
The results obtained from the air leakage tests are expressed in cubic feet per minute (cubic meter per second) per square foot (square meter) of opening. The results are intended to develop data to assist authorities having jurisdiction, and others, in determining the acceptability of through-penetration firestops with reference to the control of air movement through the assembly.
These requirements do not cover devices that penetrate fire resistive floors and walls but terminate on the opposite side, as, for example, an outlet box and fitting.
URI: http://yse.yabesh.ir/std/handle/yse/219725
Collections :
  • UL - UL
  • Download PDF : (700.9Kb)
  • Show Full MetaData Hide Full MetaData
  • Statistics

    UL 1479

Show full item record

contributor authorUL - UL
date accessioned2017-09-04T18:37:53Z
date available2017-09-04T18:37:53Z
date copyright05/23/2003
date issued2003
identifier otherJOLVAFAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std/handle/yse/219725
description abstractThese requirements cover through-penetration firestops of various materials and construction that are intended for use in openings in fire resistive wall or floor-ceiling assemblies, or both.
The method of testing through-penetration firestops as specified by these requirements consists of exposure of test samples to a fire of standard time and temperature and to an application of a hose stream. Ratings are then established on the basis of:
a) The length of time the firestop resists fire before the first development of through openings or flaming on the unexposed surface,
b) Acceptable limitation of thermal transmission, and
c) Acceptable performance under the application of the hose stream.
The method of testing also includes optional air leakage tests to determine the rate of air leakage through through-penetration firestop systems resulting from a specified air pressure difference applied across the surface of the systems.
The method of testing also includes optional water leakage tests to determine the ability of through-penetration firestop systems to resist the passage of water under a three foot pressure head. This method does not evaluate the ability of uncured firestop systems to resist such exposure.
Two ratings are established for each through-penetration firestop system: an F rating based upon flame occurrence on the unexposed side of the test sample and acceptable hose stream performance; and a T rating based on temperature rise and flame occurrence on the unexposed side of the test sample and acceptable hose stream performance.
An L rating may also be established for a through-penetration firestop system. The L rating is based on the amount of air leakage through the test sample.
An W rating may also be established for a through-penetration firestop system. The W rating is based on the water resistance of the test sample.
The method of testing through-penetration firestop systems containing piping systems for vented (drain, waste or vent) systems and closed (process or supply) systems is differentiated by the capping or non-capping of the piping systems on the unexposed side of the test assembly as described in 4.1.2.
Tests conducted in accordance with these requirements are intended to demonstrate the performance of through-penetration firestops during exposure to fire, but are not intended to determine acceptability of firestops for use after exposure to fire. These requirements do not cover the ampacity of conductors encased in through-penetration firestop materials.
The results obtained from the air leakage tests are expressed in cubic feet per minute (cubic meter per second) per square foot (square meter) of opening. The results are intended to develop data to assist authorities having jurisdiction, and others, in determining the acceptability of through-penetration firestops with reference to the control of air movement through the assembly.
These requirements do not cover devices that penetrate fire resistive floors and walls but terminate on the opposite side, as, for example, an outlet box and fitting.
languageEnglish
titleUL 1479num
titleUL Standard for Safety Fire Tests of Through-Penetration Firestops - Third Edition; Reprint with Revisions through and Including October 19, 2012en
typestandard
page46
statusActive
treeUL - UL:;2003
contenttypefulltext
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian
 
DSpace software copyright © 2017-2020  DuraSpace
نرم افزار کتابخانه دیجیتال "دی اسپیس" فارسی شده توسط یابش برای کتابخانه های ایرانی | تماس با یابش
yabeshDSpacePersian