Performance Requirements for Atmospheric Type Vacuum Breakers

contributor authorASSE - American Society of Sanitary Engineering
date accessioned2017-09-04T18:41:02Z
date available2017-09-04T18:41:02Z
date copyright01/01/2008
date issued2008
identifier otherJWFEDCAAAAAAAAAA.pdf
identifier urihttp://yse.yabesh.ir/std/handle/yse/222599
description abstractDescription
Vacuum Breakers shall be classified in two general types:
a. Atmospheric type, as described herein.
b. Pressure type (See ASSE Standard #1020, Performance Requirements for Pressure Vacuum Breaker Assembly, and ASSE Standard #1056, Spill Resistant Vacuum Breakers).
The atmospheric type design shall consist of a check valve member and an air vent that is normally closed when the device is pressurized, and open when the inlet pressure is atmospheric.
Sizes
Inlet and outlet pipe sizes shall range from 1/8 NPT to 4 NPT (3 mm to 100 mm).
Working Pressure
Devices shall be designed to operate within a working pressure of 8.0 psi (55.2 kPa) to a minimum of 125.0 psi (861.9 kPa).
Temperature Range
a. Devices limited to cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 110.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 43.3 °C + 0 °C – 1.1 °C).
b. Devices intended for hot or cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 180.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 82.2 °C + 0 °C – 1.1 °C).
languageEnglish
titleASSE 1001num
titlePerformance Requirements for Atmospheric Type Vacuum Breakersen
typestandard
page23
statusActive
treeASSE - American Society of Sanitary Engineering:;2008