ASSE 1001
Performance Requirements for Atmospheric Type Vacuum Breakers
Organization:
ASSE - American Society of Sanitary Engineering
Year: 2008
Abstract: Description
Vacuum Breakers shall be classified in two general types:
a. Atmospheric type, as described herein.
b. Pressure type (See ASSE Standard #1020, Performance Requirements for Pressure Vacuum Breaker Assembly, and ASSE Standard #1056, Spill Resistant Vacuum Breakers).
The atmospheric type design shall consist of a check valve member and an air vent that is normally closed when the device is pressurized, and open when the inlet pressure is atmospheric.
Sizes
Inlet and outlet pipe sizes shall range from 1/8 NPT to 4 NPT (3 mm to 100 mm).
Working Pressure
Devices shall be designed to operate within a working pressure of 8.0 psi (55.2 kPa) to a minimum of 125.0 psi (861.9 kPa).
Temperature Range
a. Devices limited to cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 110.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 43.3 °C + 0 °C – 1.1 °C).
b. Devices intended for hot or cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 180.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 82.2 °C + 0 °C – 1.1 °C).
Vacuum Breakers shall be classified in two general types:
a. Atmospheric type, as described herein.
b. Pressure type (See ASSE Standard #1020, Performance Requirements for Pressure Vacuum Breaker Assembly, and ASSE Standard #1056, Spill Resistant Vacuum Breakers).
The atmospheric type design shall consist of a check valve member and an air vent that is normally closed when the device is pressurized, and open when the inlet pressure is atmospheric.
Sizes
Inlet and outlet pipe sizes shall range from 1/8 NPT to 4 NPT (3 mm to 100 mm).
Working Pressure
Devices shall be designed to operate within a working pressure of 8.0 psi (55.2 kPa) to a minimum of 125.0 psi (861.9 kPa).
Temperature Range
a. Devices limited to cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 110.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 43.3 °C + 0 °C – 1.1 °C).
b. Devices intended for hot or cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 180.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 82.2 °C + 0 °C – 1.1 °C).
Collections
:
Show full item record
contributor author | ASSE - American Society of Sanitary Engineering | |
date accessioned | 2017-09-04T18:41:02Z | |
date available | 2017-09-04T18:41:02Z | |
date copyright | 01/01/2008 | |
date issued | 2008 | |
identifier other | JWFEDCAAAAAAAAAA.pdf | |
identifier uri | http://yse.yabesh.ir/std/handle/yse/222599 | |
description abstract | Description Vacuum Breakers shall be classified in two general types: a. Atmospheric type, as described herein. b. Pressure type (See ASSE Standard #1020, Performance Requirements for Pressure Vacuum Breaker Assembly, and ASSE Standard #1056, Spill Resistant Vacuum Breakers). The atmospheric type design shall consist of a check valve member and an air vent that is normally closed when the device is pressurized, and open when the inlet pressure is atmospheric. Sizes Inlet and outlet pipe sizes shall range from 1/8 NPT to 4 NPT (3 mm to 100 mm). Working Pressure Devices shall be designed to operate within a working pressure of 8.0 psi (55.2 kPa) to a minimum of 125.0 psi (861.9 kPa). Temperature Range a. Devices limited to cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 110.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 43.3 °C + 0 °C – 1.1 °C). b. Devices intended for hot or cold water service shall operate within a range from 33.0 °F + 2.0 °F – 0 °F to 180.0 °F +0 °F – 2.0 °F (0.6 °C + 1.1 °C – 0 °C to 82.2 °C + 0 °C – 1.1 °C). | |
language | English | |
title | ASSE 1001 | num |
title | Performance Requirements for Atmospheric Type Vacuum Breakers | en |
type | standard | |
page | 23 | |
status | Active | |
tree | ASSE - American Society of Sanitary Engineering:;2008 | |
contenttype | fulltext |