ASSE 1015
Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies
Organization:
ASSE - American Society of Sanitary Engineering
Year: 2009
Abstract: Description
This standard applies to two types of backflow prevention assemblies identified as:
Double Check Backflow Prevention Assembly (DC); and
Double Check Fire Protection Backflow Prevention Assembly (DCF).
These assemblies consist of two (2) independently acting check valves, internally force loaded to a normally closed position, two (2) properly located tightly closing shut-off valves per Section 1.3.2.6 and properly located test cocks per Section 1.3.2.4. These assemblies are designed and constructed to operate under intermittent or continuous pressure conditions.
This standard also applies to Manifold Double Check Backflow Prevention Assemblies consisting of two or more complete Double Check Backflow Prevention Assemblies in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold assembly. Manifold Double Check Backflow Prevention Assemblies shall include line-sized shut-off valves on each inlet and outlet of the assemblies making up the manifold.
Size Range
Connection pipe sizes shall be in accordance with Table 1.
Rated Pressure
A DC assembly shall be designed for a working pressure of at least 150.0 psi (1034.3 kPa).
A DCF assembly shall be designed for a working pressure of at least 175.0 psi (1206.7 kPa).
Temperature Range
The assemblies shall be designed for a minimum temperature range of 33.0°F to 140.0°F (0.6°C to 60.0°C).
This standard applies to two types of backflow prevention assemblies identified as:
Double Check Backflow Prevention Assembly (DC); and
Double Check Fire Protection Backflow Prevention Assembly (DCF).
These assemblies consist of two (2) independently acting check valves, internally force loaded to a normally closed position, two (2) properly located tightly closing shut-off valves per Section 1.3.2.6 and properly located test cocks per Section 1.3.2.4. These assemblies are designed and constructed to operate under intermittent or continuous pressure conditions.
This standard also applies to Manifold Double Check Backflow Prevention Assemblies consisting of two or more complete Double Check Backflow Prevention Assemblies in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold assembly. Manifold Double Check Backflow Prevention Assemblies shall include line-sized shut-off valves on each inlet and outlet of the assemblies making up the manifold.
Size Range
Connection pipe sizes shall be in accordance with Table 1.
Rated Pressure
A DC assembly shall be designed for a working pressure of at least 150.0 psi (1034.3 kPa).
A DCF assembly shall be designed for a working pressure of at least 175.0 psi (1206.7 kPa).
Temperature Range
The assemblies shall be designed for a minimum temperature range of 33.0°F to 140.0°F (0.6°C to 60.0°C).
Collections
:
Show full item record
contributor author | ASSE - American Society of Sanitary Engineering | |
date accessioned | 2017-09-04T15:42:35Z | |
date available | 2017-09-04T15:42:35Z | |
date copyright | 07/24/2009 | |
date issued | 2009 | |
identifier other | BAXENCAAAAAAAAAA.pdf | |
identifier uri | http://yse.yabesh.ir/std/handle/yse/44845 | |
description abstract | Description This standard applies to two types of backflow prevention assemblies identified as: Double Check Backflow Prevention Assembly (DC); and Double Check Fire Protection Backflow Prevention Assembly (DCF). These assemblies consist of two (2) independently acting check valves, internally force loaded to a normally closed position, two (2) properly located tightly closing shut-off valves per Section 1.3.2.6 and properly located test cocks per Section 1.3.2.4. These assemblies are designed and constructed to operate under intermittent or continuous pressure conditions. This standard also applies to Manifold Double Check Backflow Prevention Assemblies consisting of two or more complete Double Check Backflow Prevention Assemblies in parallel. The assemblies do not need to be of the same pipe size. The manifold size shall be identified by the single inlet and outlet of the manifold assembly. Manifold Double Check Backflow Prevention Assemblies shall include line-sized shut-off valves on each inlet and outlet of the assemblies making up the manifold. Size Range Connection pipe sizes shall be in accordance with Table 1. Rated Pressure A DC assembly shall be designed for a working pressure of at least 150.0 psi (1034.3 kPa). A DCF assembly shall be designed for a working pressure of at least 175.0 psi (1206.7 kPa). Temperature Range The assemblies shall be designed for a minimum temperature range of 33.0°F to 140.0°F (0.6°C to 60.0°C). | |
language | English | |
title | ASSE 1015 | num |
title | Performance Requirements for Double Check Backflow Prevention Assemblies and Double Check Fire Protection Backflow Prevention Assemblies | en |
type | standard | |
page | 28 | |
status | Active | |
tree | ASSE - American Society of Sanitary Engineering:;2009 | |
contenttype | fulltext |